ODOT CN-8011

Modbus-RTU Network Adapter


Product Feature:

CN-8011 Modbus-RTU Network Adapter

Module Overview

CN-8011 Modbus-RTU network adapter supports standard Modbus-RTU communication, it supports function code of 01/02/03/04/05/06/15/16/23, and this device could monitor the IO module communication state in real time.

 

Adapter Hardware Parameter
πŸ‘‰ System Power Nominal Reverse Protection: YES: 24Vdc, Range: 9-36Vdc
πŸ‘‰ Power Consumption: 30mA@24Vdc
πŸ‘‰ Internal Bus Supply
πŸ‘‰ Current Max: 2.5A@5VDC
πŸ‘‰ Isolation: System Power to Field Power Isolation
πŸ‘‰ Power Supply Nominal: 24Vdc, Range:22-28Vdc
πŸ‘‰ Field Power Current: Max. DC 8A
πŸ‘‰ IO Modules Supported: 32 pcs
πŸ‘‰ Wiring: Max.1.5mmΒ²(AWG 16)
πŸ‘‰ Mounting Type: 35mm DIN-Rail
πŸ‘‰ Size: 115*51.5*75mm
πŸ‘‰ Weight: 130g

 

Environment Specification
πŸ‘‰ Operation Temperature -40~85℃
πŸ‘‰ Operation Humidity 5%-95% (No Condensation)
πŸ‘‰ Protection: IP20

 

Modbus-RTU Parameter
πŸ‘‰ Protocol: Modbus-RTU/ASCII
πŸ‘‰ Function Code: 01 / 02 / 03 / 04 / 05 / 06 / 15 / 16
πŸ‘‰ Baud Rate: 2400~115200bps
πŸ‘‰ Station No. : 1~63(Dial-code switch configuration), 64~247(Software configuration)
πŸ‘‰ Interface: 5 Pin screw terminal
πŸ‘‰ Data Bits: 7, 8
πŸ‘‰ Parity Checking: None, Even, ODD
πŸ‘‰ Stop Bit: 1,Β  2
πŸ‘‰ Max. bus length: 1200m(RS485, 2400 baud rate)
πŸ‘‰ Terminal resistance and offset resistance: Dial-code switch configuration

Categories: ,