ODOT CT-5321

Modbus Serial Port Module


Product Feature:

CT-5321 Modbus Serial Port Module

Module Description

The Modbus serial port module supports 1 channel RS485/RS232 /RS422(optional), supports Modbus RTU/ASCII protocol, and supports master, slave and free transparent transmission mode.

The serial Module CT-5321 could be applied with the adapter modules, so it could convert Modbus into other protocols such as Modbus TCP, Profinet, EtherCAT, EtherNet/IP, etc. When the module is used, serial port parameters and Modbus instructions should be configured in IO Config software.

Devices with RS485/RS232/RS422 interface, which support modbus-RTU/ASCII, could be applied with CT-5321 to realize interconnection with upper PLC or upper computers. CT-5321 could be applied with devices such as: PLC, DCS, remote IO, VFD, motor start protection device, intelligent high and low voltage electrical apparatus, power measurement device, intelligent field measurement equipment and instruments, etc.

 

General parameters

Power Max.500mA@5.0Vdc
Isolation I/O to internal bus: opto-couple isolation (3KVrms)
Field Power Nominal:24Vdc, Range:22-28Vdc
Wiring I/O Wiring: Max.1.5mm²(AWG 16)
Mounting Type 35mmDIN-Rail
Size 115*14*75mm
Weight 65g

 

Environment Specification

Operational
Temperature
-40~85℃
Operational
Humidity
5%~95% RH(No Condensation)
Protection Class IP20

 

Serial Port Parameters

Note: M represents the valid parameters of master mode, S represents the valid parameters of slave mode, and F represents the valid parameters of free transparent transmission mode

M/S/F:Channel
Number
1Channel
M/S/F:Interface RS485/RS232/RS422
M/S:Protocol Modbus RTU/ASCII
M/S/F:Working
Mode
Modbus Master, Slave, Transparent Transmission
M/S/F:Baud Rate 300bps-500Kbps
M/S/F:Data Bit Bit 7, Bit 8
M/S/F:Parity
Checking
None, Odd, Even
M/S/F:Stop Bit Bit1, Bit2
M/S/F:
Character Interval
1.5t-200t
F: Byte Order
Conversion
Prohibit, Enable
M/F:Response
Timeout
Customized, default: 1000
M/F: Polling
Timeout
Customized, default: 100
M: Read Data
Processing Mode
Hold the last input value, clear the input value
M: Data
Output Mode
Polling, event triggering (data changes)
M: Module
Control Enable
Prohibit, Enable
M: Module
Control Mode
Level trigger (continuously valid), rising edge trigger (single
valid)
M: Power on
Event Output
Prohibit, Enable
S:Slave ID Customized, default: 1
S:Response
Time
Customized, default: 50